Residual Chlorine/ Chlorine DiOxide Controller

Home / Liquid Analysis / Residual Chlorine/ Chlorine DiOxide Controller
Products Code : PC-TRC400/ERC400

Need Advice?
Ask Our Experts!  +91 937 618 1613

Description

The residual chlorine controller has a built-in sensor, which has the characteristics of high measurement accuracy, fast response time and low maintenance cost. The residual chlorine meter outputs 4~20mA standard signal and RS485 signal, which can be connected to various regulators, and can be connected to two-position regulators, time proportional regulators, non-linear regulators and classic PID regulators according to requirements, which can be combined into various types. Residual chlorine control system.

 

Applications:

  • Secondary water supply
  • Tap water
  • Pool water
  • Water works
  • Agricultural drinking water

 

Features:

  • The electrode measurement is accurate and the response speed is fast
  • LCD with backlight, easy and intuitive operation
  • With automatic temperature compensation, pH manual compensation function
  • Restore factory function to avoid data loss by misoperation
  • Isolated 4-20mA standard signal can realize signal remote transmission
  • Range can be switched manually
  • A variety of calibration methods are convenient for on-site adjustment

 

Technical Specifications:

Residual Chlorine Controller
Display 7 inch touch screen
Cabinet Size 400mm×300mm×200mm, Window size: 155mm×87mm
Measuring Range Residual chlorine: (0~5) mg/L, Temperature: (0.1~40.0)℃
Transmit Output 4-20mA )Optional)
Communication RS485
Load Resistance ≤750Ω
Environment Humidity ≤95% no condensation
Power Supply 220VAC
IP Rating IP43
Residual Chlorine Electrode
Measurement Content HCLO、CLO2
Measuring System Microelectronics MEMS technology, special membrane structure
Measuring Range (0~5)mg/L
Acuracy When ≤0.1mg/L, the absolute error is ±0.01mg/L; When ≥0.1mg/L, ±5% of the measured value or ±0.02mg/L (whichever is greater)
Resolution 0.01
Polarization Time When using for the first time, first pass water for 2 hours in chlorinated water, and then power on for half an hour
Response Time Less than 30s after polarization is completed
Minimum Conductivity ≥100us/cm, can not be used for ultrapure water
Operating Temperature (0~40)℃ (non-condensing)
Temperature Compensation Pt1000 with built-in integrated automatic compensation
Max Pressure 4 Bar
Recommended Flow Rate ≥0.03m/s in flow cell
pH Range (5~9) pH, below 5 will damage the membrane head
Maximum Chlorine Concentration ≥5ppm
Power Supply Standard 24V DC±2V; optional 12V DC±2V
Power Consumption 1.56W
Communication RS485
Cable Length Standard 3 meters, others can be customized
Probe Weight 210g
Thread Size NPT 3/4
Connection Method 5-pin waterproof aviation plug
Moisture Proof Material PVC and Viton® O-ring seals

 

Wiring:

1 -- RS485A

2 -- RS485B

3 -- 4-20mA+

4 -- 4-20mA-

 

Sensor Wiring:

Core Number 1 2 3 4 5
Sensor Wire Red Black Yellow Green White
Signal 24VDC+ 24VDC- RS485A RS485B Ground

 

Dimensions:

     

                                                                                               Unit: mm

 

Ordering Information:

PC-TRC400-RT1-O0-D1-A2-V1

PC-TRC400
RT1 Type (0~5)mg/L
O0 Transmit Output No O/P
O1 4-20mA
D1 Communication RS485
A2 Relay Output 2 Relay O/Ps
V1 Power Supply 220VAC (140-240VAC)

 

PC-ERC400-ST1-C1-D1-V1-CS3

PC-ERC400
ST1 Type Compact type
C1 Compensation Type PT1000 temp compensation
D1 Communication RS485
V1 Power Supply 24VDC (22~26VDC)
V3 12VDC (10~14VDC)
CS3 Cable Length 3m
CSXX XXm